CSI MasterFormat Division 26 Template · Electrical

CSI Division 26 Electrical Submittal Packet Template

Free CSI Division 26 Electrical submittal packet template covering EMT Conduit (26 05 33), Panelboards (26 24 16), Wiring Devices (26 27 26), Disconnect Switches (26 28 16), LED Troffers (26 51 19), and Exit/Emergency Lighting (26 52 13).

CSI Sections Covered
6 Sections
Seeded Cut Sheets
6 Verified Items
PDF Output Branding
100% White-Label

Interactive Pre-Submission Audit

Architect Pre-Submission Checklist — Division 26 (Electrical)

Verify every coordination point before exporting your submittal PDF to avoid costly Revise & Resubmit delays.

0 / 7 Verified (0%)

Pre-Loaded Manufacturer Literature

Division 26 CSI Cut-Sheet Specification Schedule

Load All 6 Items in Compiler
CSI SectionManufacturer & ProductStandards & ListingsKey Engineering SpecsAction
26 24 16
Panelboards
NF Series 480Y/277V Lighting & Appliance Panelboard
Schneider Electric / Square D · NF442L2C-225A-65K

Commercial 480Y/277V 3-phase 4-wire bolt-on copper-bus panelboard with 225A main lugs, 42 circuit capacity, 65 kAIC fully rated EDB/EGB/EJB branch breaker architecture, and door-in-door NEMA 1 trim.

UL 67 Panelboards ListedNEMA PB 1 Panelboards StandardNFPA 70 (NEC Article 408) CompliantUL 50 Type 1 Galvanized Steel Enclosure
  • Voltage & Phasing: 480Y/277V AC, 3-Phase, 4-Wire, 60 Hz solid neutral
  • Bus Rating & Material: 225A silver-plated copper busbar, 100% rated neutral + ground bar
  • Short-Circuit Rating: 65 kAIC fully rated (series-rated option available up to 200 kAIC)
Load Item
26 51 19
LED Interior Lighting
BLT2 2x4 Architectural Volumetric LED Troffer
Acuity Brands / Lithonia Lighting · 2BLT4-40L-ADP-EZ1-LP840

Low-profile 2x4 recessed LED volumetric luminaire with curved linear-prismatic acrylic diffuser, eldoLED 0-10V dimming down to 1%, and L85 > 60,000-hour lumen maintenance for commercial ceilings.

UL 1598 & UL 8750 Damp Location ListedDLC 5.1 Premium Qualified (131 lm/W)IC Rated / ASTM E283 Air-Tight HousingFCC Title 47 Part 15 Class A Compliant
  • Delivered Lumens: 4,120 nominal lumens @ 4000K CCT, >= 82 CRI (R9 > 12)
  • Input Wattage / Efficacy: 31.4W system input · 131.2 lumens/watt efficacy
  • Driver & Dimming: Universal 120–277V eldoLED 0–10V dimming to 1% (flicker <1%)
Load Item
26 05 33
Raceway and Boxes for Electrical Systems
Hot-Dip Galvanized Electrical Metallic Tubing (EMT) Conduit
Wheatland Tube · WT-EMT-3/4IN-10FT

Precision cold-rolled electric-resistance welded steel EMT raceway featuring hot-dip galvanized exterior zinc coating and slick interior organic coating for low-friction conductor pulling.

UL 797 Electrical Metallic Tubing — SteelANSI C80.3 Steel EMT SpecificationNFPA 70 (NEC Article 358) Recognized EGCBuy American Act / Domestic Melted Steel
  • Trade Size & Length: 3/4 in nominal trade size (0.922 in OD) · 10 ft standard lengths
  • Wall Thickness: 0.049 in nominal cold-rolled mild carbon steel wall
  • Exterior Coating: Hot-dip galvanized pure zinc with chromate & clear topcoat
Load Item
26 27 26
Wiring Devices
Extra Heavy-Duty Industrial Spec-Grade 20A Duplex Receptacle
Hubbell Wiring Device-Kellems · HBL5362I-20A-125V

Commercial/industrial specification-grade 20A 125V NEMA 5-20R duplex receptacle with one-piece brass mounting strap, triple-wipe brass power contacts, and impact-resistant nylon face.

UL 498 Attachment Plugs & ReceptaclesFederal Specification W-C-596 Heavy DutyNEMA WD-6 Configuration 5-20RCSA C22.2 No. 42 Certified
  • Electrical Rating: 20A, 125V AC, 2-Pole 3-Wire Grounding (NEMA 5-20R)
  • Power Contacts: 0.037 in solid brass triple-wipe bypass contacts for high retention
  • Mounting Strap: One-piece 0.050 in solid brass wrap-around bridge with integral ground
Load Item
26 28 16
Enclosed Switches and Circuit Breakers
Heavy-Duty 60A 600V 3-Pole Non-Fusible NEMA 3R Disconnect Switch
Eaton · DH362URK-60A-3R

Heavy-duty 60A 600V AC 3-pole non-fusible safety disconnect switch housed in a rainproof NEMA 3R galvanized steel enclosure with visible-blade quick-make/quick-break mechanism.

UL 98 Enclosed & Dead-Front SwitchesNEMA KS 1 Heavy-Duty Type HD SwitchNFPA 70 (NEC Article 430) Motor DisconnectIBC / OSHPD Seismic Certified Enclosure
  • Ampere & Voltage Rating: 60A continuous, 600V AC / 250V DC, 3-Pole non-fusible
  • Horsepower Rating: 50 HP max @ 480V 3-Phase / 60 HP max @ 600V 3-Phase
  • Short-Circuit Rating: 10 kAIC (up to 200 kAIC when protected by Class J/R upstream fuses)
Load Item
26 52 13
Emergency and Exit Lighting
EVE Series LED Combination Exit Sign & Emergency Egress Unit
Current / Dual-Lite · EVE-R-W-NI-SD

Thermoplastic LED combination exit sign with dual adjustable 1.5W emergency egress heads, maintenance-free nickel-cadmium battery for 90-minute runtime, and automated Spectron self-diagnostics.

UL 924 Emergency Lighting (Damp Location)NFPA 101 Life Safety Code CompliantNFPA 70 (NEC Article 700) Emergency SystemsCalifornia Title 20 CEC Efficiency Certified
  • Legend & Illumination: 6 in high RED LED letters (3/4 in stroke), snap-out directional chevrons
  • Emergency Lamp Heads: Two adjustable 1.5W LED track/swivel heads (260 lm total, 22 ft spacing)
  • Battery & Runtime: Sealed maintenance-free Ni-Cad battery, 90-min UL 924 minimum runtime
Load Item

Field Review Intelligence

Top 4 Division 26 “Revise & Resubmit” Traps

Common review comments that stall procurement approvals — and how to eliminate them before submitting to the GC and Architect.

Trap #126 24 16

Series-Rated Panelboards Submitted Where Fully Rated AIC Is Specified

Why it gets rejected: Submitting series-rated breakers when project specifications mandate fully rated 65 kAIC equipment due to selective coordination or healthcare emergency systems.

How to prevent it: Explicitly call out '65 kAIC Fully Rated' and copper busbar construction on the panelboard spec sheet and cover summary.

Trap #226 51 19

Lighting Dimming Driver Incompatibility (10% vs. 1% 0-10V or DALI)

Why it gets rejected: Submitting standard 10% dimming drivers when the lighting control spec requires 1% low-end dimming (eldoLED EZ1) or nLight/DALI digital interfaces.

How to prevent it: Verify the exact driver option code in the full luminaire catalog string against the lighting fixture schedule.

Trap #326 52 13

Wrong Exit Sign Legend Color or Missing Self-Diagnostics

Why it gets rejected: Submitting red exit letters in a municipality requiring green letters, or omitting UL 924 self-testing circuitry specified by the owner.

How to prevent it: Confirm AHJ exit color code, chevron knockouts, and Spectron/self-diagnostic suffix before compiling the lighting package.

Trap #426 28 16

Non-Fusible Disconnect Submitted Where HVAC Equipment Requires MOP Fuses

Why it gets rejected: Providing a non-fusible disconnect switch when rooftop HVAC nameplate data specifies 'Maximum Fuse Size' rather than 'Maximum Overcurrent Protection (HACR/Circuit Breaker)'.

How to prevent it: Verify rooftop unit and fan nameplates with Div 23 so fusible Class J/R switches are submitted wherever fuses are mandated.

Submittal Reference FAQ

Division 26 Submittal Frequently Asked Questions

What CSI sections are covered in this Division 26 Electrical submittal template?

This template covers six core electrical CSI MasterFormat sections: EMT Raceway (26 05 33), 480Y/277V Panelboards (26 24 16), 20A Spec-Grade Wiring Devices (26 27 26), NEMA 3R Heavy-Duty Disconnect Switches (26 28 16), 2x4 LED Troffers (26 51 19), and UL 924 LED Exit/Emergency Combos (26 52 13).

Can I add Square D Qwik-Grip / Eaton Bid Manager or lighting rep fixture cut sheets?

Yes. Load the Division 26 preset in the Web Compiler, drop your distributor or lighting rep PDF cut sheets into the browser vault, assign CSI codes, and compile a clean white-label submittal package with auto-TOC.

Does the compiled electrical submittal packet include an Architect/Engineer review stamp box?

Yes. The white-label cover sheet includes a toggleable Architect/Engineer of Record review stamp block with Approved, Approved as Noted, Revise & Resubmit, and Rejected checkboxes plus signature and date lines.

How does organizing Division 26 submittals by CSI MasterFormat prevent rejections?

Electrical engineers review gear, distribution, wiring devices, and lighting fixtures against distinct specification sections. Separating each CSI code with divider tabs and an exact Table of Contents cuts review turnaround and prevents 'incomplete submittal' rejections.

Multi-Trade CSI Library

Explore All CSI Division Submittal Templates

Division 08

Openings Submittal Template

6 cut sheets · 4 CSI sections · Pre-submission checklist

Division 23

HVAC Submittal Template

6 cut sheets · 6 CSI sections · Pre-submission checklist

Division 26Current

Electrical Submittal Template

6 cut sheets · 6 CSI sections · Pre-submission checklist